PPL Announces SPS for Susquehanna-Jenkins
Mar 11, 2014
PPL announced a special protection scheme to prevent overloads on its Susquehanna-Jenkins 230kv transmission line.
PPL announced a special protection scheme to prevent overloads on its Susquehanna-Jenkins 230 kV transmission line.
According to PPL’s presentation to the Planning Committee last week, the protection would be activated under NERC N-1-1 contingencies, for example the loss of both the Susquehanna-Lackawanna 500 kV line and Mountain-Lackawanna 230 kV lines.
The scheme would trip the Stanton #1 and #2 breakers at Jenkins five minutes after the Susquehanna-Jenkins line exceeds 100% of its emergency rating and one minute after it exceeds its loadshed rating.
The scheme will be removed following the rebuild of Susquehanna-Jenkins (RTEP project b2269), which is scheduled for completion in summer 2018.